Modbus TCP Protocol

Component Type: Protocol

Status: Implemented

Overview

CProtoModbusTcp is a Modbus TCP slave protocol object that maps NxModbus callbacks to Dawn IO.

Implementation

  • Supported register group types: MODBUS_TYPE_COIL, MODBUS_TYPE_COIL_PACKED, MODBUS_TYPE_DISCRETE, MODBUS_TYPE_DISCRETE_PACKED, MODBUS_TYPE_INPUT, MODBUS_TYPE_HOLDING, MODBUS_TYPE_SEEKABLE.

  • Overlap in the same register class is rejected at configuration (assert + error return).

  • MODBUS_TYPE_COIL_PACKED uses Modbus bit encoding for bool IO: 0 -> bit 0, nonzero -> bit 1.

  • MODBUS_TYPE_INPUT and MODBUS_TYPE_HOLDING support mixed-width IO (16/32/64-bit) inside one group.

  • Register shadow buffer is allocated only for notify groups. Non-notify groups read directly from IO.

Register Management

The mapping between Dawn IO objects and Modbus registers is handled by the CProtoModbusRegs base class. This logic is shared across all Modbus transport implementations (RTU, TCP).

Configuration

Kconfig

  • CONFIG_DAWN_PROTO_MODBUS: enables Modbus protocol support.

  • CONFIG_DAWN_PROTO_MODBUS_TCP: enables the TCP transport.

  • CONFIG_DAWN_PROTO_MODBUS_TCP_PORT: default TCP listen port.

  • CONFIG_DAWN_PROTO_MODBUS_TCP_ADDR: default Modbus slave address.

YAML

protocols:
  - id: modbus1
    type: modbus_tcp
    config:
      port: 502
      registers:
        - type: coil
          notify: 0
          start: 0
          bindings:
            - coil1
            - coil2
        - type: discrete_packed
          notify: 1
          start: 100
          bindings:
            - di1
            - di2
            - di3
        - type: holding
          notify: 0
          start: 1000
          bindings:
            - holding1
        - type: input
          notify: 0
          start: 2000
          bindings:
            - input1

Supported fields:

  • config.port: TCP listen port.

  • config.registers: register group definitions.

Supported registers[*].type values:

  • coil

  • discrete

  • coil_packed

  • discrete_packed

  • input

  • holding

  • seekable

Supported registers[*] fields:

  • type: register group type.

  • notify: enable change notification shadowing for the group.

  • start: first register or bit address.

  • bindings: IOs mapped into the group.

External Control

ControlIO: supported.

CProtoModbusTcp supports runtime start/stop control through CIOControl. When stopped, Modbus polling/service loop is inactive. When started again, register servicing resumes.

TriggerIO: not supported.